Weber 80A NH00C Fuse Link
Description
This is an NH fuse link, size 00C, manufactured by Weber. It has a nominal current rating of 80A and a voltage rating of 500V AC. The gG characteristic makes it suitable for general-purpose applications, primarily for the protection of cables and lines against overloads and short circuits.
Specifications
- Manufacturer: Weber
- Type: NH Fuse Link
- Model: NH 00 C KTF/gG
- Part Number: A 1500580
- Current Rating: 80A
- Voltage Rating: 500V AC
- Size: NH00C
- Characteristic: gG (also compatible with gL applications)
- Breaking Capacity: 100kA
Label Info
- NH00C KTF
- 80A 500V~
- I1 100kA
- gL - gG
Application
Designed for use in industrial low-voltage distribution boards, switchgear, and control panels to protect equipment from fault currents. Ideal for protecting cables, power lines, and other electrical apparatus.
Country of Origin
This product is manufactured in Germany.
CO2 Impact
Opting for this refurbished fuse link saves approximately 1.8 kg of CO2 compared to manufacturing a new one. This saving is equivalent to the emissions from charging a smartphone over 200 times.
Availability
This item is in stock and ready for immediate dispatch. Order now from PLC2Day for expert support and fast delivery.
FAQ
What is the difference between gG and gL characteristics?gG and gL are largely interchangeable. 'gL' was the older VDE standard designation, while 'gG' is the current IEC standard for general-purpose line protection fuses. A fuse marked with both, like this one, complies with both standards.
Can this NH00C fuse be used in a standard NH00 fuse base?Yes, the 'C' in NH00C refers to a compact body design, but it maintains the standard blade contacts and dimensions to fit in any standard NH size 00 fuse base or switch-disconnector.
What is the breaking capacity (interrupting rating) of this fuse?As indicated on the label (I1 100kA), this fuse has a high-rupturing or breaking capacity of 100,000 Amperes (100kA). This means it can safely interrupt very high short-circuit currents without damage.
PLC2DAY is not an authorized distributor, reseller, or representative of the products featured on this website. All product names, trademarks, brands, and logos used on this site are the property of their respective owners.
Last Update: Friday, March 13, 2026
More Information
| Item Number | NH00C KTF/gG 80A 500V 120kA 1500580 |
|---|---|
| Brands | WEBER |
| HS Code | 85361010 |
| EAN | 4013391005583 |
| HS Description | Industrial Fuse Link |
| Manufacturer | WEBER |
| Product Condition | Factory New |
| Packing Condition | Original Packing Packing |