IFM IG0011 IGA2005-AB0A
In stock
Backorder allowed
Out of stock
Description / IFM IG0011 IGA2005-AB0A
- Inductive sensor
- Cable-Length: 1.90 mtrs
- With combined AC/DC output stage
- Wide voltage range
- Two-wire technology
- Robust metal housing for use in harsh industrial environments
- ccc, ce, ukca, cul
- Product features
- Output function, make contact
- Switching distance [mm]: 5
- Housing: cylindrical thread
- Dimensions [mm]: M18 x 1 / L = 80
- Electrical properties
- Supply voltage [V]: 20...250 AC/DC
- Protection class: II
- Reverse polarity protection: no
- Exits, Output function, make contact
- Max. voltage drop switching output DC [V]: 6
- Max. voltage drop switching output AC [V]: 6.5
- Minimum load current [mA]: 5
- Max. quiescent current [mA]: 2.5 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC)
- Continuous current load of switching output AC [mA]: 250; (350 (...50 °C))
- Continuous current load of switching output DC [mA]: 100
- Short-term current load of the switching output [mA]: 2200; (20ms / 0.5Hz)
- Switching frequency AC [Hz]: 25
- Switching frequency DC [Hz]: 50
- Short-circuit proof: no
- Protected against overload: no
- Range, Switching distance [mm]: 5
- Actual switching distance (Sr) [mm]: 5 ± 10%
- Working distance [mm]: 0...4.05
- Accuracy/deviations
- Correction factor, steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminum: 0.3 / copper: 0.2
- Hysteresis [% of Sr]: 1...15
- Switch point drift [% of Sr]: -10...10
- Environmental variables
- Ambient temperature [°C]: -25...80
- Protection class: IP67
- Admissions/testing
- EMC, EN 61000-4-2 ESD, 4 kV CD / 8 kV AD, EN 61000-4-3 HF edited, 3 V/m, EN 61000-4-4 Burst, 2 kV, EN 61000-4-6 HF cable related, 3 Q, EN 55011, class B
- MTTF [years]: 609
- UL Approval, Ta, 0...40 °C
- Enclosure type: Type 1, industrial power supplies
- Hazardous voltage, File number UL
IFM IGA2005-AB0A is an advanced industrial flow meter designed for precise measurement. This item is commonly used in industries such as manufacturing, chemical processing, and water treatment. Purchase this high-quality flow meter at PLC2Day for reliable and accurate flow measurement in your industrial applications.
More Information
Item Number | IG0011 IGA2005-AB0A |
---|---|
Brands | IFM |
HS Code | Upon Request |
EAN | Not Applicable |
HS Description | Inductive sensor: Cable-Length: 1,90 mtrs |
Manufacturer | IFM |
Product Condition | Used |
Packing Condition | PLC2Day Packing |